SPEL Synthetic/Midel Oil Separators

The introduction of synthetic cooling oil in transformers has dramatically improved the fire safety record for grid-based substations, these oils are classified as K-class fluids with a high fire point of >300°C to IEC 61039.While the use of such a fluid reduces fire risk and associated costs, the difference in specific gravity (SG = 0.97 at 20°C) presents challenges for capturing this type of oil in a conventional separator in the event of an oil leak or spill. This has resulted in SPEL conducting extensive testing and redesign to ensure that Midel can be safely and reliably captured in the advanced SPEL Midel Separator.A further technical advance in the SPEL Midel Oil Separator is the inclusion of a motorised Automatic Closure Device (ACD) which will shut down in the event of a catastrophic spill.
Learn about the SPEL Tank Shell construction – Proven & Time-Tested Quality you can rely on

For Midel Transformer Fluids

Introduction and operation

The SPEL Midel Oil Separator models are designed for high performance and long service life between maintenance periods.

The Midel range is a two chamber system for enhanced performance and reduced maintenance.

An alarm will sound and/or message an alarm on site or to a control room and automatically close off the separation chamber via the auto closing device, closed by a motorised valve. This is actuated by an oil alarm, closing the outlet in the case of a spillage emergency or when the maximum oil capacity has been reached.

Product Ranges

300 Series Range

(1.8m inside diameter):

NS 6 – NS 10

Catchment area: 333m2 – 556m2

400 Series Range

(2.6m inside diameter):

NS 20 – NS 60

Catchment area: 1,111m2 – 3,333m2

500 Series Range

(3.5m inside diameter):

NS 80 – NS 100

Catchment area: 4,444m2 – 5,555m2

Larger sizes available upon request

Automatic Closure Device

The SPEL Midel Oil Separators have a closure device by way of a motorised valve actuated by an oil alarm. The alarm will sound and/or message an alarm on site or to a control room and automatically close off the separation chamber from the outlet in the case of a spillage emergency or when the maximum oil capacity has been reached.

Shell Design

Designed with reference to BS EN 13121. All tank shells carry the SPEL 25 Year Warranty and life expectancy in excess of 50 years.

Shell Specifications

Different tank shell specifications are available dependent upon tank invert levels, ground conditions and ground water levels. (See Installation Guidance section)

Inlet/Outlet Connections

160/225/300mm diameter PVCU socket/spigot.

450, 600, 750, 900 and 1200mm diameter GRP spigot available, for connecting to site pipework via Flex-Seal/Band-Seal or similar flexible couplings.

The nine inlet/outlet options below are available to assist with design and installation.

The ‘heart’ of the SPEL Separators is the unique long life, low maintenance coalescer unit/s

The coalescer unit is mounted in the second chamber, providing a coalescence process for the separation of smaller globules of light liquid pollutants before final discharge to the surface water drain.

Being incorporated in the second chamber prevents contamination or blockage of the coalescer insert in water. It can be simply lifted out for cleaning during routine maintenance.

Typical applications are:

  • Power/substations using Midel Oil transformers.

Features

Tank shell designed in accordance with BS EN 13121
  • Filament wound shell – the embodiment of strength and durability – yet lightweight.
  • Life expectancy in excess of 50 years.
  • Smooth, high gloss internal corrosion resistant surface.
  • External ‘flow coat’ water penetration barrier.
  • Robust stainless steel coalescer unit with long-life, high-volume foam insert and lifting handle.
  • Coalescer unit/s in second chamber protected from bulk of oil and silt.
  • The M range for Midel oil have a closure device by way of a motorised valve actuated by an oil alarm.
  • Good access to all parts for desludging.
  • Sampling point incorporated into outlet.
  • Generous access for desludging and servicing of the ACD and coalescer unit/s
  • Sized for working capacity PLUS fuel/oil and silt containment, ensuring optimum performance between maintenance periods.
  • Generous sizing extends maintenance free periods and reduces desludging costs.
  • Dip pipe inlet for minimum turbulence and to prevent inflammable vapours passing upstream in drainage system.
Model
Series
Nominal Size (NS)
Catchment Area (m2)
Oil Storage (L)
Silt Capacity (L)
Overall Length (mm)
Inlet Invert (mm)
Base to Inlet (mm)
Base to Outlet (mm)
Optimum Inlet dia.** (mm)


Flow (l/s)



L




P006 2C/SC/M
300
6
333
60
600
3,200
540
1,610
1,550
160
P010 2C/SC/M
300
10
556
100
1,000
5,070
540
1,610
1,550
160
P015 2C/SC/M
300
15
833
150
1,500
6,570
550
1,600
1,500
225
P020 2C/SC/M
400
20
1,111
200
2,000
5,250
625
2,425
2,325
225
P025 2C/SC/M
400
25
1,389
250
2,500
6,170
625
2,425
2,325
225
P030 2C/SC/M
400
30
1,667
300
3,000
7,400
625
2,425
2,325
300
P040 2C/SC/M
400
40
2,222
400
4,000
9,930
For details, please contact our Technical Sales Team
300
P060 2C/SC/M
400
60
3,333
600
6,000
13,710
For details, please contact our Technical Sales Team

300
P080 2C/SC/M
500
80
4,444
800
8,000
10,040
For details, please contact our Technical Sales Team

300
P100 2C/SC/M
500
100
5,555
1,000
10,000
12,530
For details, please contact our Technical Sales Team

450
Larger sizes available upon request*SPEL Separators are designed for a maximum flow (NS/NSB) but can be fitted with larger than the recommended maximum connection size IN/OUT or with the addition of adapters providing the maximum flow (NS/NSB) cannot be exceeded or any increase in the operating level in the SPEL Separator to cause the captured pollutants to escape into the vent connections or through access shaft connections. Any overriding of the above criteria could jeopardise performance to the European Standard BS EN 858-1.

SPEL extension access shafts

All SPEL Separator Systems have a large range of technical accessories to ease maintenance and monitoring.

Circular access shafts are supplied in 450, 600, 700, 900 and 1200mm diameter. Rectangular shafts are supplied in 800, 900 and 1000mm X 1000/1250/1500mm. GRP ladders can be incorporated for more access, complete with stainless steel fixings.

Rectangular Shafts
Stub Access Shafts
Flanged joint stub access shaft with extension shaft
600,750 and 900mm diameter.
Socket joint stub access shaft with extension shaft
600, 750, 900 and 1200mm diameter

200/300 Series

Shafts can be laminated onto the tank up to a maximum height of 1.2m. Above this height extension shafts can be supplied separately for on-site fitting during installation.

400 Series

Shafts up to 400mm high are laminated onto the tank. Above this height extension shafts can be supplied separately for on-site fitting during installation.

500 Series

Shafts up to 300mm high are laminated onto the tank. Above this height extension shafts can be supplied separately for on-site fitting during installation.

600 Series

Stub access shafts are fitted 100mm high and extension access shafts fitted as 500 series. Above this height extension shafts can be supplied separately for on-site fitting during installation.

Extension Shafts

These are supplied in 500mm increments and are available in different laminate specs to suit site-specific invert levels and applications.

SPEL Coalescer Guide Rail Systems

Note: only applicable to units fitted with the SPEL Coalescer

Normal servicing of the smaller SPEL Separators frequently requires emptying the unit completely. Guide rails provide access for the coalescer units to be taken out, cleaned and returned and guided accurately to their seating positions. However larger SPEL Separators may only require the hydrocarbon pollutants and silt to be removed.

In order to limit the servicing to sucking off the fuel/oil from the top and the silt from the bottom guide rails are required to ensure coalescer units are replaced into their correct positions.

The system is robust, manufactured throughout in stainless steel and the action positive, leaving no doubt the coalescer unit is located properly.

Brackets fixed to the top and bottom of the coalescer unit simply engage the stainless steel guide rail fixed to the top of the stub access shaft. The coalescer is then lowered in the normal way, being guided at the correct angle into the conical base unit which locates the coalescer unit into its final position.

Extension guide rails can be incorporated into SPEL extension shafts to suit (preferably when ordered with the separator).

SPEL Coalescer Lifting, Locating and Locking system (3L)

SPEL coalescer units lowered into the separator with the SPEL guide rail system are easily guided into the base unit’s conical moulding to automatically sit correctly.

However, when the separator is full of water, debris or silt accumulated over a period, this could prevent the coalescer unit from re-seating correctly after servicing.

The coalescer unit lifting/locating/locking system provides assurance the coalescer unit is seated correctly and can be locked into position to prevent tampering.

The system is particularly suitable in SPEL Separator + Econoskim® systems where the total contents of the separator are not emptied on servicing.

The system comprises a robust stainless steel lifting and lowering handle that locates on the guide rail system. When the coalescer unit is correctly located in the conical seating in the separator, the handle will align with guide rail top bracket i.e.. the handles slotted holes with the top bracket clip locking groove, see diagram.

When aligned the stainless steel clip can be located through the slots and lock into position on the top bracket.

The stainless steel lifting handle can be extended to suit deep tank inverts and provide easy access for lifting manually or with the SPEL tripod and hoist.

 

Automatic Alarms/Monitoring Systems

Alarm systems are available for all SPEL separators. These include probes for oil, silt and high level. There are also a range of control panels including solar power, more detail on our alarm systems can be found in Section 8.
Control Panels

Mains Powered Separator Alarms

For silt, oil and high level detection, compatible with the below alarm probes.

Solar Alarms

Available with optional flashing beacon, and GMS/ SMS communication, also compatible with the below alarm probes.

Alarm Probes

idOil-OIL oil probe

Detects oil and indicates when the treatment system’s oil storage is full.This probe is required in order for a treatment device to comply with BS EN 858.

idOil-SLU silt probe

Monitors the silt layer in the treatment system and indicates when the silt layer has reached its maximum level.

idOil-LiQ high liquid level probe

Indicates when the liquid level in the treatment system rises excessively e.g. in an outlet blockage situation.

SPEL tripod and hoist

Where surface water run-off has a high silt content the coalescer units can become filled, making them heavy to lift out. In order to facilitate easy withdrawal of coalescer units the SPEL tripod and hoist is recommended.

SPELGuard Commissioning, RAF Base

SPEL Econoskim

The SPEL Separator + Econoskim System is a patented system designed to maintain oil separators at peak performance for as long as possible. It does this by skimming the oil from the surface of the separator and transferring it to a separate containment tank for simple collection by a waste oil contractor thus reducing costs and further protecting the environment. For more information, click here.

1. When the SPEL constant monitoring system detects the level of fuel/oil pollutants has reached the pre-determined volume, the skimmers are brought into operation, transferring these pollutants from the SPEL separator to the SPEL Tankstor® containment tank. When the transference of light liquid pollutants has been completed, the system automatically stops the skimming process and re-sets.

2. During the skimming cycle a small amount of water is transferred from the SPEL separator into the SPEL Tankstor® containment tank. In order to maximise the capacity of the SPEL Tankstor® containment tank for pollutants, accumulated water is automatically transferred back to the SPEL separator.

3. The process repeats automatically every time pollutants reach the pre-determined volume. When the SPEL Tankstor® containment tank is 90% full, the SPEL constant monitoring system signals ‘EMPTY NOW’ with an audible and visual alarm.

Request A Quotation

For further information phone our sales hotline 01743 457977, email sales@spelproducts.co.uk or Click the button below.
Model
Series
Nominal Size (NS)
Catchment Area (m2)
Oil Storage (L)
Silt Capacity (L)
Overall Length (mm)
Inlet Invert (mm)
Base to Inlet (mm)
Base to Outlet (mm)
Optimum Inlet dia.** (mm)


Flow (l/s)



L




P006 2C/SC/M
300
6
333
60
600
3,200
540
1,610
1,550
160
P010 2C/SC/M
300
10
556
100
1,000
5,070
540
1,610
1,550
160
P015 2C/SC/M
300
15
833
150
1,500
6,570
550
1,600
1,500
225
P020 2C/SC/M
400
20
1,111
200
2,000
5,250
625
2,425
2,325
225
P025 2C/SC/M
400
25
1,389
250
2,500
6,170
625
2,425
2,325
225
P030 2C/SC/M
400
30
1,667
300
3,000
7,400
625
2,425
2,325
300
P040 2C/SC/M
400
40
2,222
400
4,000
9,930
For details, please contact our Technical Sales Team
300
P060 2C/SC/M
400
60
3,333
600
6,000
13,710
For details, please contact our Technical Sales Team

300
P080 2C/SC/M
500
80
4,444
800
8,000
10,040
For details, please contact our Technical Sales Team

300
P100 2C/SC/M
500
100
5,555
1,000
10,000
12,530
For details, please contact our Technical Sales Team

450

Request a Quote for SPEL Synthetic/Midel Oil Separators

Fill out the form below with your details and any info you wish to be considered by our team and we will be in touch shortly. 

This is the SPEL Puraceptor single chamber model sizing chart. For the difference between single and two chamber models see the explanation below under operation.

Model
Series
Nominal Size (NS)
Catchment Area (m2)
Oil Storage (L)
Silt Capacity (L)
Overall Length* (mm)
Overall Diameter (mm)
Inlet Invert (mm)
Base to Inlet (mm)
Base to Outlet (mm)
Optimum In/Out Pipe Diameter** (mm)
Number of Access Shafts(dia. mm)


Flow (l/s)



L

A
B
C

450
600
750
900
1200
P004 1C/SC
200
4
222
40
400
1,720
1,225
630
1,110
1,050
160
1
P006 1C/SC
200
6
333
60
600
2,310
1,225
630
1,110
1,050
160
1
P010 1C/SC
200
10
556
100
1,000
3,410
1,225
630
1,110
1,050
160
1
P015 1C/SC
300
15
833
150
1,500
3,200
1,875
350
1,800
1,740
225
1
1
P020 1C/SC
300
20
1,111
200
2,000
3,540
1,875
350
1,800
1,740
225
1
1
FP 1C/SC
300
20
1,111
200
2,000
4,290
1,875
350
1,800
1,740
225

1
P030 1C/SC
300
30
1,667
300
3,000
4,420
1,875
390
1,760
1,700
300
1
1
P040 1C/SC
300
40
2,222
400
4,000
5,760
1,875
390
1,760
1,700
300
1
1
P050 1C/SC
300
50
2,778
500
5,000
7,060
1,875
390
1,760
1,700
300
1
1
P065 1C/SC
400
65
3,611
650
6,500
4,860
2,700
425
2,625
2,525
300
1
2
P080 1C/SC
400
80
4,444
800
8,000
5,700
2,700
425
2,625
2,525
300
1
2
P100 1C/SC
400
100
5,555
1,000
10,000
7,400
2,700
475
2,575
2,475
450
1
2
P125 1C/SC
400
125
6,944
1,250
12,500
8,580
2,700
475
2,575
2,475
450
1
2
P150 1C/SC
400
150
8,333
1,500
15,000
10,180
2,700
475
2,575
2,475
450
1
2
P165 1C/SC
400
165
9,166
1,650
16,500
11,200
2,700
500
2,550
2,450
450
2
1
1
P200 1C/SC
400
200
11,110
2,000
20,000
13,710
2,700
660
2,390
2,290
600
2
1
1
P250 1C/SC
400
250
13,888
2,500
25,000
16,750
2,700
660
2,390
2,290
600
2
1
2
P280 1C/SC
400
280
15,555
2,800
28,000
18,800
2,700
660
2,390
2,290
600
1
2
2
P300 1C/SC
500
300
16,665
3,000
30,000
12,410
3,650
805
3,070
2,970
750
1
2
2
P400 1C/SC
500
400
22,220
4,000
40,000
15,760
3,650
805
3,070
2,970
750
2
2
2
P500 1C/SC
500
500
27,775
5,000
50,000
20,530
3,650
955
2,920
2,820
900
2
2
1
1
P500 1C/SC
600
500
27,775
5,000
50,000
16,040
4,150
925
3,250
3,150
900
2
2
1
1
P600 1C/SC
600
600
33,330
6,000
60,000
19,080
4,150
925
3,250
3,150
900
2
2
2
P700 1C/SC
600
700
38,888
7,000
70,000
21,460
4,150
925
3,250
3,150
900
3
2
3
P800 1C/SC
600
800
44,440
8,000
80,000
23,020
4,150
925
3,250
3,150
900
3
2
2
1
All of the above models are available without silt capacity, below are selected models for size comparison. The P1000 model is only available in non silt format.
P050 1C
300
50
2,778
500
5,070
1875
390
1,760
1,700
300
1
P065 1C
400
65
3,611
650
3,710
2,700
425
2,625
2,525
300

2
P100 1C
400
100
5,555
1,000
5,250
2,700
475
2,575
2,475
450

2
P125 1C
400
125
6,944
1,250
6,090
2,700
475
2,575
2,475
450
2
P165 1C
400
165
9,166
1,650
7,960
2,700
500
2,550
2,450
450
2

1
P250 1C
400
250
13,888
2,500
11,830
2,700
660
2,390
2,290
600
2

2
P300 1C
400
300
16,665
3,000
14,120
2,700
660
2,390
2,290
600
2

2
P500 1C
500
500
27,775
5,000
14,340
3,650
955
2,920
2,820
900
2
2
1
1
P500 1C
600
500
27,775
5,000
11,470
4,150
925
3,250
3,150
900
2
2
1
1
P700 1C
600
700
38,888
7,000
15,880
4,150
925
3,250
3,150
900
3
2
3
P1000 1C
600
1,000
55,550
10,000
21,407
4,150
925
3,250
3,150
900
3
2
1
3

*Overall length subject to inlet/outlet and orientation.

**SPEL Separators are designed for a maximum flow (NS/NSB) but can be fitted with larger than the recommended maximum connection size IN/OUT or with the addition of adapters providing the maximum flow (NS/NSB) cannot be exceeded or any increase in the operating level in the SPEL Separator to cause the captured pollutants to escape into the vent connections or through access shaft connections. Any overriding of the above criteria could jeopardise performance to the European Standard BS EN 858-1.

Note: Model FP1C/SC is a special Forecourt separator with 7600 litre spillage holding capacity. Click here for more information on Forecourt Separators.

This is the SPEL Puraceptor two chamber model sizing chart. For the difference between single and two chamber models see the explanation below under operation.

Model
Series
Nominal Size (NS)
Catchment Area (m2)
Oil Storage (L)
Silt Capacity (L)
Overall Length* (mm)
Overall Diameter (mm)
Inlet Invert (mm)
Base to Inlet (mm)
Base to Outlet (mm)
Optimum In/Out Pipe Diameter** (mm)
Number of Access Shafts(dia. mm)


Flow (l/s)



L

A
B
C

450
600
750
900
1200
P006 2C/SC
200
6
333
60
600
3,050
1,225
340
1,200
1,140
160
1
1
P010 2C/SC
200
10
556
100
1,000
4,690
1,225
340
1,200
1,140
160
1
1
P015 2C/SC
300
15
833
150
1,500
4,015
1,875
350
1,800
1,740
225
2
P020 2C/SC
300
20
1,111
200
2,000
4,015
1,875
350
1,800
1,740
225
2
FP 2C/SC***
300
20
1,111
200
2,000
5,500
1,875
350
1,800
1,740
225
2
P025 2C/SC
300
25
1,389
250
2,500
4,290
1,875
350
1,800
1,740
225
2
P030 2C/SC
300
30
1,667
300
3,000
4,420
1,875
390
1,760
1,700
300
1
2
P035 2C/SC
300
35
1,944
350
3,500
5,070
1,875
390
1,760
1,700
300
1
2
P040 2C/SC
300
40
2,222
400
4,000
5,760
1,875
390
1,760
1,700
300
1
2
P050 2C/SC
300
50
2,778
500
5,000
7,060
1,875
390
1,760
1,700
300
1
2
P065 2C/SC
300
65
3,611
650
6,500
9,180
1,875
390
1,760
1,700
300
1
2
P080 2C/SC
400
80
4,444
800
8,000
5,700
2,700
425
2,625
2,525
300
1
1
P100 2C/SC
400
100
5,555
1,000
10,000
7,400
2,700
475
2,575
2,475
450
1
1
P125 2C/SC
400
125
6,944
1,250
12,500
8,580
2,700
475
2,575
2,475
450
2
1
P150 2C/SC
400
150
8,333
1,500
15,000
10,180
2,700
500
2,550
2,450
450
2
1
P200 2C/SC
400
200
11,110
2,000
20,000
13,710
2,700
660
2,390
2,290
600
1
2
1
P250 2C/SC
400
250
13,888
2,500
25,000
16,752
2,700
660
2,390
2,290
600
2
1
2
P300 2C/SC
500
300
16,665
3,000
30,000
12,530
3,650
675
3,200
3,100
600
1
2
1
P400 2C/SC
500
400
22,220
4,000
40,000
15,980
3,650
675
3,200
3,100
600
2
2
2
P500 2C/SC
500
500
27,775
5,000
50,000
20,530
3,650
955
2,920
2,820
900
2
2
1
1
P500 2C/SC
600
500
27,775
5,000
50,000
16,260
4,150
925
3,250
3,150
900
2
1
1
1
P600 2C/SC
600
600
33,330
6,000
60,000
19,080
4,150
925
3,250
3,150
900
2
2
3
P700 2C/SC
600
700
38,888
7,000
70,000
22,270
4,150
925
3,250
3,150
900
3
2
3
P800 2C/SC
600
800
44,440
8,000
80,000
23,020
4,150
925
3,250
3,150
900
3
2
2
1
P900 2C/SC
600
900
50,000
9,000
90,000
24,658
4,150
925
3,250
3,150
900
3
2
1
2

*Overall length subject to inlet/outlet and orientation.

**SPEL Separators are designed for a maximum flow (NS/NSB) but can be fitted with larger than the recommended maximum connection size IN/OUT or with the addition of adapters providing the maximum flow (NS/NSB) cannot be exceeded or any increase in the operating level in the SPEL Separator to cause the captured pollutants to escape into the vent connections or through access shaft connections. Any overriding of the above criteria could jeopardise performance to the European Standard BS EN 858-1.

Note: Model FP2C/SC is a special Forecourt separator with 7600 litre spillage holding capacity. Click here for more information on Forecourt Separators.

[
ModelSeriesMeals per Day*NSGTank Length (mm)Internal Diameter (mm)Overall Capacity (L)Grease Capacity (L)Inlet Invert (m)Base to Inlet (mm)Base to Outlet(mm)Optimum In/Out Pipe Diameter** (mm)Number of Access Shafts (dia. mm)
LABC600
GS200/200020040042,0401,2002,0001601,0201,0009401602
GS200/300020060062,9301,2003,0002401,0201,0009401602
GS200/400020090093,8101,2004,0003601,0201,0009401602
GS200/50002001100114,7001,2005,0004401,0201,0009401602
GS200/60002001400145,5781,2006,0005601,0201,0009401602
GS300/58603001400142,6901,8005,8605601,6001,6001,5501602
GS300/92703001800184,0151,8009,2707201,6001,6001,5501602
GS300/182003004000407,6201,80018,20016001,6001,6001,5501602
ModelSeriesMax. Flow*Silt Capacity (L)Overall Length*Internal Diameter (mm)Opt In/Out Pipe Diameter (mm)Number of Access Shafts (dia. mm)Inlet Invert (mm)
Flow (l/s)L600A
WDS 200/10002001.12501.171,200160mm1
WDS 200/20002002.25002.051,200160mm1
WDS 200/30002003.37002.931,200160mm1
WDS 200/40002004.51,0003.821,200160mm1
WDS 200/50002005.61,2504.71,200160mm1
WDS 200/60002006.71,5005.591,200160mm1
WDS 200/70002007.81,7506.481,200160mm1
WDS 200/800020092,0007.361,200160mm1
WDS 200/9000200102,2508.251,200160mm1
WDS 200/10,000200112,5009.131,200160mm1
WDS 300/400030051,0001.951,800160mm1
WDS 300/600030071,5002.761,800160mm1
WDS 300/800030092,0003.541,800160mm1
WDS 300/10,000300122,5004.291,800160mm1
ModelSeriesNominal Size (NB)Catchment Area (M2)Oil Storage (L)Silt Capacity (L)Overall Length* (mm)Overall Diameter (mm)Inlet Invert (mm)Base to Inlet (mm)Base to Outlet (mm)Optimum In/Out pipe Diameter** (mm)Number of Access Shafts (dia. mm)
Flow (l/s)ABC450600750
FR004 SC2004222404001,72012256301,1101,0501601
FR006 SC2006333606002,2701,2256301,1101,0501601
FR010 SC200105561001,0003,4101,2256301,1101,0501601
FR015 SC300158331501,5002,7601,8753501,8001,7402251
FR020 SC300201,1112002,0003,2001,8753501,8001,7402251
FS2 SC300201,1112002,0004,2901,8753501,8001,7402251
FR030 SC300301,6673003,0004,4201,8753901,7601,7003001
FR040 SC300402,2224004,0005,7601,8753901,7601,7003001
FR050 SC300502,7785005,0007,0601,8753901,7601,7003001
FR065 SC400653,6116506,5004,8102,7004252,6252,52530011
FR080 SC400804,4448008,0005,7002,7004252,6252,52530011
FR100 SC4001005,5551,00010,0007,4002,7004752,5752,47545011
FR125 SC4001256,9441,25012,5008,5802,7004752,5752,47545011
FR150 SC4001508,3331,50015,00010,1802,7004752,5752,47545011
FR165 SC4001659,1661,65016,50011,2002,7005002,5502,4504502
FR200 SC40020011,1102,00020,00013,7102,7006602,3902,2906002
FR250 SC40025013,8882,50025,00016,7502,7006602,3902,2906002
ModelSeriesNominal Size (NB)Catchment Area (M2)Oil Storage (L)Silt Capacity (L)Overall Length* (mm)Overall Diameter (mm)Inlet Invert (mm)Base to Inlet (mm)Base to Outlet (mm)Optimum In/Out pipe Diameter** (mm)Number of Access Shafts (dia. mm)
Flow (l/s)ABC450600750
FR040300402,2224004,0201,8753901,7601,7003001
FR050300502,7785005,0701,8753901,7601,7003001
FR065400653,6116503,7102,7004252,6252,52530011
FR080400804,4448004,4002,7004252,6252,52530011
FR1004001005,55510005,2502,7004752,5752,47545011
FR1254001256,94412506,0902,7004752,5752,47545011
FRI504001508,33315007,4002,7004752,5752,47545011
FR1654001659,16616507,9602,7005002,5502,4504502
FR20040020011,11020009,6002,7006602,3902,2906002
FR25040025013,888250011,8302,7006602,3902,2906002
FR30040030016,665300014,1202,7006602,3902,2906002
FR400500400222,2224,000optional*3,6503

*Overall length subject to inlet/outlet size and orientation

**SPEL Separators are designed for a maximum flow (NS/NSB) but can be fitted with larger than the recommended maximum connection size IN/OUT or with the addition of adapters providing the maximum flow (NS/NSB) cannot be exceeded or any increase in the operating level in the SPEL Separator to cause the captured pollutants to escape into the vent connections or through access shaft connections. Any overriding of the above criteria could jeopardise performance to the European Standard BS EN 858-1.

Note: Model FS2SC is a special forecourt unit with 7600 litre spillage holding capacity.

ModelSeriesNominal Size (NS)Catchment Area (m2)Oil Storage (L)Silt Capacity (L)Overall Length* (mm)Overall Diameter (mm)Inlet Invert (mm)Base to Inlet (mm)Base to Outlet (mm)Optimum In/Out Pipe Diameter** (mm)Number of Access Shafts (dia. mm)
Flow (l/s)LABC4507509001200
P006 2C/SC/NG2006333606003,05012254271,1101,05016011
P010 2C/SC/NG200105561001,0004,7001,2254271,1101,0501603
P015 2C/SC/NG300158331501,5004,0201,8755401,6101,5502253
P020 2C/SC/NG300201,1112002,0004,0201,8755401,6101,5502253
P025 2C/SC/NG300251,3892502,5004,2901,8755401,6101,5502253
P030 2C/SC/NG300301,6673003,0005,0701,8755501,6001,50030021
P040 2C/SC/NG300402,2224004,0006,5701,8755501,6001,50030021
P050 2C/SC/NG300502,7785005,0008,2601,8755501,6001,50030021
P065 2C/SC/NG300653,6116506,50010,2201,8755501,6001,500300121
P065 2C/SC/NG400653,6116506,5005,4702,7006652,3852,285300111
P080 2C/SC/NG400804,4448008,0006,1702,7006652,3852,285300111
P100 2C/SC/NG4001005,5551,00010,00074002,70066523852285450111
P125 2C/SC/NG4001256,9441,25012,5009,6002,7007652,2852,185450121
P150 2C/SC/NG4001508,3331,50015,00011,2002,7007902,2802,180450121
P200 2C/SC/NG40020011,1102,00020,00016,4002,7009402,1302,030600221
P300 2C/SC/NG50030016,6653,00030,00012,5303,6508753,0002,900600221
P400 2C/SC/NG50040022,2204,00040,00016,3303,6508753,0002,900600322
ModelSeriesNominal Size (NS)Catchment Area (m2)Oil Storage (L)Silt Capacity (L)Overall Length* (mm)Overall Diameter (mm)Inlet Invert (mm)Base to Inlet (mm)Base to Outlet (mm)Optimum In/Out Pipe Diameter* (mm)Number of Access Shafts (dia. mm)
Flow (l/s)LABC7509001200
FP 1C/SCClass 1 Forecourt SeparatorSingle Chamber with Silt Capture300201,1112002,0004,2901,8753501,8001,7402251
FP 2C/SCClass 1 Forecourt SeparatorTwo Chamber with Silt Capture300201,1112002,0005,5001,8753501,8001,7402252
FS2 SCClass 2 Forecourt SeparatorSingle Chamber with Silt Capture300201,1112002,0004,2901,8753501,8001,7402251
Model
Series
Nominal Size (NS)
Catchment Area (m2)
Oil Storage (L)
Silt Capacity (L)
Overall Length* (mm)
Overall Diameter (mm)
Inlet Invert (mm)
Base to Inlet (mm)
Base to Outlet (mm)
Optimum In/Out Pipe Diameter** (mm)
Number of Access Shafts(dia. mm)


Flow (l/s)



L

A
B
C

450
600
750
900
1200
P006 2C/SC
200
6
333
60
600
3,050
1,225
340
1,200
1,140
160
1
1
P010 2C/SC
200
10
556
100
1,000
4,690
1,225
340
1,200
1,140
160
1
1
P015 2C/SC
300
15
833
150
1,500
4,015
1,875
350
1,800
1,740
225
2
P020 2C/SC
300
20
1,111
200
2,000
4,015
1,875
350
1,800
1,740
225
2
FP 2C/SC***
300
20
1,111
200
2,000
5,500
1,875
350
1,800
1,740
225
2
P025 2C/SC
300
25
1,389
250
2,500
4,290
1,875
350
1,800
1,740
225
2
P030 2C/SC
300
30
1,667
300
3,000
4,420
1,875
390
1,760
1,700
300
1
2
P035 2C/SC
300
35
1,944
350
3,500
5,070
1,875
390
1,760
1,700
300
1
2
P040 2C/SC
300
40
2,222
400
4,000
5,760
1,875
390
1,760
1,700
300
1
2
P050 2C/SC
300
50
2,778
500
5,000
7,060
1,875
390
1,760
1,700
300
1
2
P065 2C/SC
300
65
3,611
650
6,500
9,180
1,875
390
1,760
1,700
300
1
2
P080 2C/SC
400
80
4,444
800
8,000
5,700
2,700
425
2,625
2,525
300
1
1
P100 2C/SC
400
100
5,555
1,000
10,000
7,400
2,700
475
2,575
2,475
450
1
1
P125 2C/SC
400
125
6,944
1,250
12,500
8,580
2,700
475
2,575
2,475
450
2
1
P150 2C/SC
400
150
8,333
1,500
15,000
10,180
2,700
500
2,550
2,450
450
2
1
P200 2C/SC
400
200
11,110
2,000
20,000
13,710
2,700
660
2,390
2,290
600
1
2
1
P250 2C/SC
400
250
13,888
2,500
25,000
16,752
2,700
660
2,390
2,290
600
2
1
2
P300 2C/SC
500
300
16,665
3,000
30,000
12,530
3,650
675
3,200
3,100
600
1
2
1
P400 2C/SC
500
400
22,220
4,000
40,000
15,980
3,650
675
3,200
3,100
600
2
2
2
P500 2C/SC
500
500
27,775
5,000
50,000
20,530
3,650
955
2,920
2,820
900
2
2
1
1
P500 2C/SC
600
500
27,775
5,000
50,000
16,260
4,150
925
3,250
3,150
900
2
1
1
1
P600 2C/SC
600
600
33,330
6,000
60,000
19,080
4,150
925
3,250
3,150
900
2
2
3
P700 2C/SC
600
700
38,888
7,000
70,000
22,270
4,150
925
3,250
3,150
900
3
2
3
P800 2C/SC
600
800
44,440
8,000
80,000
23,020
4,150
925
3,250
3,150
900
3
2
2
1
P900 2C/SC
600
900
50,000
9,000
90,000
24,658
4,150
925
3,250
3,150
900
3
2
1
2
Model
Series
Nominal Size (NS)
Catchment Area (m2)
Oil Storage (L)
Silt Capacity (L)
Overall Length* (mm)
Overall Diameter (mm)
Inlet Invert (mm)
Base to Inlet (mm)
Base to Outlet (mm)
Optimum In/Out Pipe Diameter** (mm)
Number of Access Shafts(dia. mm)


Flow (l/s)



L

A
B
C

450
600
750
900
1200
P004 1C/SC
200
4
222
40
400
1,720
1,225
630
1,110
1,050
160
1
P006 1C/SC
200
6
333
60
600
2,310
1,225
630
1,110
1,050
160
1
P010 1C/SC
200
10
556
100
1,000
3,410
1,225
630
1,110
1,050
160
1
P015 1C/SC
300
15
833
150
1,500
3,200
1,875
350
1,800
1,740
225
1
1
P020 1C/SC
300
20
1,111
200
2,000
3,540
1,875
350
1,800
1,740
225
1
1
FP 1C/SC
300
20
1,111
200
2,000
4,290
1,875
350
1,800
1,740
225

1
P030 1C/SC
300
30
1,667
300
3,000
4,420
1,875
390
1,760
1,700
300
1
1
P040 1C/SC
300
40
2,222
400
4,000
5,760
1,875
390
1,760
1,700
300
1
1
P050 1C/SC
300
50
2,778
500
5,000
7,060
1,875
390
1,760
1,700
300
1
1
P065 1C/SC
400
65
3,611
650
6,500
4,860
2,700
425
2,625
2,525
300
1
2
P080 1C/SC
400
80
4,444
800
8,000
5,700
2,700
425
2,625
2,525
300
1
2
P100 1C/SC
400
100
5,555
1,000
10,000
7,400
2,700
475
2,575
2,475
450
1
2
P125 1C/SC
400
125
6,944
1,250
12,500
8,580
2,700
475
2,575
2,475
450
1
2
P150 1C/SC
400
150
8,333
1,500
15,000
10,180
2,700
475
2,575
2,475
450
1
2
P165 1C/SC
400
165
9,166
1,650
16,500
11,200
2,700
500
2,550
2,450
450
2
1
1
P200 1C/SC
400
200
11,110
2,000
20,000
13,710
2,700
660
2,390
2,290
600
2
1
1
P250 1C/SC
400
250
13,888
2,500
25,000
16,750
2,700
660
2,390
2,290
600
2
1
2
P280 1C/SC
400
280
15,555
2,800
28,000
18,800
2,700
660
2,390
2,290
600
1
2
2
P300 1C/SC
500
300
16,665
3,000
30,000
12,410
3,650
805
3,070
2,970
750
1
2
2
P400 1C/SC
500
400
22,220
4,000
40,000
15,760
3,650
805
3,070
2,970
750
2
2
2
P500 1C/SC
500
500
27,775
5,000
50,000
20,530
3,650
955
2,920
2,820
900
2
2
1
1
P500 1C/SC
600
500
27,775
5,000
50,000
16,040
4,150
925
3,250
3,150
900
2
2
1
1
P600 1C/SC
600
600
33,330
6,000
60,000
19,080
4,150
925
3,250
3,150
900
2
2
2
P700 1C/SC
600
700
38,888
7,000
70,000
21,460
4,150
925
3,250
3,150
900
3
2
3
P800 1C/SC
600
800
44,440
8,000
80,000
23,020
4,150
925
3,250
3,150
900
3
2
2
1
All of the above models are available without silt capacity, below are selected models for size comparison. The P1000 model is only available in non silt format.
P050 1C
300
50
2,778
500
5,070
1875
390
1,760
1,700
300
1
P065 1C
400
65
3,611
650
3,710
2,700
425
2,625
2,525
300

2
P100 1C
400
100
5,555
1,000
5,250
2,700
475
2,575
2,475
450

2
P125 1C
400
125
6,944
1,250
6,090
2,700
475
2,575
2,475
450
2
P165 1C
400
165
9,166
1,650
7,960
2,700
500
2,550
2,450
450
2

1
P250 1C
400
250
13,888
2,500
11,830
2,700
660
2,390
2,290
600
2

2
P300 1C
400
300
16,665
3,000
14,120
2,700
660
2,390
2,290
600
2

2
P500 1C
500
500
27,775
5,000
14,340
3,650
955
2,920
2,820
900
2
2
1
1
P500 1C
600
500
27,775
5,000
11,470
4,150
925
3,250
3,150
900
2
2
1
1
P700 1C
600
700
38,888
7,000
15,880
4,150
925
3,250
3,150
900
3
2
3
P1000 1C
600
1,000
55,550
10,000
21,407
4,150
925
3,250
3,150
900
3
2
1
3
ModelNominal Size (NSB)Peak Flow (l/s)Catchment Area (m2)Oil Storage (L)Silt Storage (L)Length (mm)Internal Diameter (mm)Inlet Invert (mm)Base to Inlet (mm)Base to Outlet (mm)Optimum in/out Pipe Diameter (mm) for Orientation*Number of Access Shafts A-C Diameter (mm)
Flow (l/s)NSB x 15NSB x 100LWABC750*900
103 C1/SC3301,667453001,5501,3005001,015965160
204 C1/SC4402,222604001,8601,2005501,3501,3003001
206 C1/SC6603,333906002,1201,2005501,3501,3003001
208 C1/SC8804,4441208002,2701,2005501,3501,3003001
210 C1/SC101005,5561501,0002,9201,2005501,3501,3003001
212 C1/SC121206,6671801,2003,5701,2005601,3501,3003001
215 C1/SC151508,3332251,5004,2371,2005601,3501,3003001
320 C1/SC2020011,1113002,0003,2001,8007001,4501,350450
325 C1/SC2525013,8893752,5003,5401,8007001,4501,350450
330 C1/SC3030016,6674503,0004,4201,8007001,4501,35045011
340 C1/SC4040022,2226004,0005,7601,8007401,4101,3104501
345 C1/SC4545025,0006754,5006,5701,8007401,4101,3104501
350 C1/SC5050027,7787505,0007,0601,8007401,4101,3104501
460 C1/SC6060033,3339006,0004,4002,6009502,1002,00060011
470 C1/SC7070038,8891,0507,0005,2502,6009502,1002,00060011
480 C1/SC8080044,4441,2008,0006,1702,6009502,1002,00060011
4100 C1/SC1001,00055,5561,50010,0007,4002,6001,1001,9501,85075011
4125 C1/SC1251,25069,4441,87512,5009,0502,6001,1001,9501,85075011
4150 C1/SC1501,50083,3332,25015,0009,9502,6001,1001,9501,8507502
4160 C1/SC1601,60088,8892,40016,00011,8302,6001,2501,8001,70075012
5180 C1/SC1801,800100,0002,70018,0007,4703,5001,1852,6902,55090012
5200 C1/SC2002,000111,0003,00020,0008,5303,5001,1852,4252,3251,20012
5250 C1/SC2502,500139,0003,75025,00010,0403,5001,1852,4252,3251,20012
6300 C1/SC3003,000167,0004,50030,00010,3104,0001,3252,8502,6751,20012
6350 C1/SC3503,500194,0005,25035,00011,5004,0001,3252,8502,6751,20023
6400 C1/SC4004,000222,0006,00040,00012,6904,0001,3252,8502,6751,20023
6500 C1/SC5005,000278,0007,50050,00015,8704,0001,3252,8502,6751,20024
6600 C1/SC6006,000333,0009,00060,00018,2604,0001,3252,8502,6751,20014
6700 C1/SC7007,000389,00010,50070,00022,2504,0001,3252,8502,6751,20025
6500 C15005,00027.87,500Nil11,9104,1501,3252,8502,6751,20014
6600 C16006,00033.39,000Nil13,5104,1501,3252,8502,6751,20014
6700 C17007,00038.910,500Nil16,6504,1501,3252,8502,6751,20015
6800 C18008,00044.412,000Nil19,8904,1501,3252,8502,6751,20016
ModelSeriesTreated Flow Rate (l/s)Maximum Design Storm Flow (l/s)Catchment area* (m²)Head Loss Storm Flow (mm)Overall Diameter (mm)Overall Chamber Height (mm)Inlet to Base (mm)Inlet Invert (mm)Silt Capacity (L)Hydrocarbon Capacity (L)Pipe Size dia. (mm)Access Opening (mm)
SHV 200/30200301224,0001801,2252,6801,6001,080360220300Ø750
SHV 300/70300702809,3332551,8253,8002,4001,4001,200900450Ø900
SHV 400/20040020065026,6653502,7005,0003,3001,7003,4502,000600Ø1,200
SHV 500/40050040090053,3335003,5405,3903,0002,3905,0004,800750Ø1,200
ModelSeriesMax. Flow (l/s)Catchment Area Based on 65mm/hrOil Storage (L)Silt Capacity (L)Tank Length (mm)Internal Diameter (mm)Inlet Invert (mm)Base to Inlet (mm)Base to Outlet (mm)Optimum in/out Pipe Diameter* (mm)Number of Access Shafts (dia. mm)
ABC4506007509001,200
P004/1C/ESR2004222404001,7101,2206301,1101,0501601
P006/1C/ESR2006333606002,3101,2206301,1101,0501601
P010/1C/ESR200105561001,0003,4001,2206301,1101,0501601
P015/1C/ESR300158331501,5003,2001,8003501,8001,74022511
P020/1C/ESR300201,1112002,0003,5401,8003501,8001,74022511
P030/1C/ESR300301,6673003,0004,4201,803901,7601,70030011
P040/1C/ESR300402,2224004,0005,7601,8003901,7601,70030011
P050/1C/ESR300502,7785005,0007,0601,8003901,7601,70030011
P065/1C/ESR400653,6116506,5004,8102,6004252,6252,52530012
P080/1C/ESR400804,4448008,0005,7002,6004252,6252,52530012
P100/1C/ESR4001005,5551,00010,0007,4002,6004752,5752,47545012
P125/1C/ESR4001256,9441,25012,5008,5802,6004752,5752,47545012
P150/1C/ESR4001508,3331,50015,00010,1802,6004752,5752,47545012
P165/1C/ESR4001659,1661,65016,50011,2002,6005002,5502,45045012
P200/1C/ESR40020011,1102,00020,00013,7102,6006602,3902,290600121
P250/1C/ESR40025013,8882,50025,00016,7502,6006602,3902,290600122
P280/1C/ESR40028015,5552,80028,00018,8002,6006602,3902,290600122
P300/1C/ESR50030016,6653,00030,00012,4103,5008053,0702,970750122
P400/1C/ESR50040022,2204,00040,00015,7603,5008053,0702,970750222
P500/1C/ESR50050027,7755,00050,00020,5303,5009552,9202,8209002211
P500/1C/ESR60050027,7755,00050,00016,0404,0009253,2503,1509002211
P600/1C/ESR60060033,3306,00060,00019,0804,0009253,2503,150900222
P700/1C/ESR60070038,8887,00070,00021,4704,0009253,2503,150900323
P800/1C/ESR60080044,4408,00080,00023,0204,0009253,2503,1509003221
P900/1C/ESR60090049,8469,00090,00024,6584,0009253,2503,150900323
ModelSeriesTreated Flow RateMaximum FlowConnectible / Catchment area (m²)*Oil Storage (litres)Silt Capacity (litres)Tank Length (mm)Internal Diameter (mm)Inlet Invert (mm)Base to Inlet (mm)Base to Outlet (mm)Optimum in / out pipe diameter ** (mm)Number of Access Shafts A-C*** (dia. mm)
LABC7509001200
210C1/ESR200101001,3331501,0002,9201,2205501,3501,3003001
212C1/ESR200121201,60018012003,5701,2205501,3501,3003001
215C1/ESR200151502,0002251,5004,2371,2205501,3501,3003001
320C1/ESR300202002,6653002,0003,2001,8007001,4501,350450
325C1/ESR300252503,3333752,5003,5351,8007001,4501,350450
330C1/ESR300303004,0004503,0004,4201,8007001,4501,35045011
340C1/ESR300404005,3336004,0005,7601,8007401,4101,3104501
345C1/ESR300454506,0006754,5006,5631,8007401,4101,3104501
350/C1/ESR300505006,6657505,0007,0601,8007401,4101,3104501
460C1/ESR400606008,0009006,0004,4002,6009502,1002,00060011
470C1/ESR400707009,3331,0507,0005,2502,6009502,1002,00060011
480C1/ESR4008080010,6651,2008,0006,1702,6009502,1002,00060011
4100C1/ESR4001001,00013,3331,50010,0007,4002,6001,1001,9501,85075011
4125C1/ESR4001251,25016,6651,87512,5009,0002,6001,1001,9501,85075011
4150C1/ESR4001501,50020,0002,25015,0009,9302,6001,1001,9501,8507502
4160C1/ESR4001601,60021,3332,40016,00011,8302,6001,2501,9501,85075012
5180C1/ESR5001801,80024,0002,70018,0007,4723,5001,1852,6902,55090012
5200C1/ESR5002002,00026,6653,00020,0008,5303,5001,1852,5702,3551,20012
5250C1/ESR5002502,50033,3333,75025,00010,0403,5001,1852,6902,3551,200
6300C1/ESR6003003,00040,0004,50030,00010,3104,0001,3252,8502,6751,20012
6350C1/ESR6003503,50046,6655,25035,00011,5004,0001,3252,8502,6751,20023
6400C1/ESR6004004,00053,3336,00040,00012,6904,0001,3252,8502,6751,20023
6500C1/ESR6005005,00066,6657,50050,00015,8804,0001,3252,8502,6751,20024
6600C1/ESR6006006,00080,0009,00060,00018,2564,0001,3252,8502,6751,20015
6700C1/ESR6007007,00093,33310,50070,00022,2504,0001,3252,8502,6751,200

Live Chat

jQuery(function ($) { $(document).on('click', '#spel-tabs .elementor-button, #spel-tabs .elementor-button-link', function (e) { const $btn = $(this); const $wrap = $btn.closest('.elementor-element'); const targetId = $btn.attr('data-target-title-id') || $wrap.attr('data-target-title-id'); if (!targetId) return; e.preventDefault(); const $title = $('#spel-tabs #' + CSS.escape(targetId)); if ($title.length) { $title.trigger('click'); $title[0].scrollIntoView({ behavior: 'smooth', block: 'start' }); } }); });jQuery(function ($) { // Delegate clicks from any Elementor button inside the tabs widget $(document).on('click', '#spel-tabs .switch-to-specs', function (e) { e.preventDefault(); const $title = $('#spel-tabs #specs'); // your tab TITLE button if ($title.length) { $title.trigger('click'); // lets Elementor open the "Specification Chart" tab $title[0].scrollIntoView({ behavior: 'smooth', block: 'start' }); } }); });